Makpower is a trusted BIS-marked Distribution Transformer manufacturer, offering energy-efficient and reliable solutions certified by CPRI and ERDA. Built as per IS:1180 standards, these transformers are designed for optimum power distribution in utilities and commercial sectors. With both copper and aluminium wound options, Makpower ensures strict compliance with mandated loss levels.
Range: Makpower manufactures BIS-certified Distribution Transformers with capacities up to 2500 KVA, in voltage class up to 33 kV. These transformers are designed to serve various rural, urban, and industrial power networks, offering durability, energy efficiency, and long-term service under all load conditions.
Prime grade CRGO steel laminations precision cut to minimize core losses & magnetizing current.
Engineered cooling ducts & high dielectric insulation system designed for severe duty thermal overloads.
Robust mechanical clamping and reinforced coil bracing to withstand electrodynamic short-circuit forces.
Available with automatic On-Load Tap Changer (OLTC) or manual Off-Circuit Tap Switch based on application.
• Standards: Designed as per IS:1180 (Part-1)/2014
Makpower’s BIS Distribution Transformers are available in multiple types to meet different utility specifications and grid standards:
• Energy Efficient: Complies with BIS star-rating norms for reduced operational losses
• Utilities: Power distribution to residential and commercial load centers
• Testing & Certification: Approved by CPRI and ERDA for BIS compliance
• Pre-Sales Consultation: Technical experts guide transformer selection per load requirements
| S.N. | Rating (KVA) | Voltage Ratio (kv) | %Z at 750C (Tol as per is 2026) | Level 1 | Level 2 | Level 3 | ||||
|---|---|---|---|---|---|---|---|---|---|---|
| Max. Total Loss at 50% Load | Max. Total Loss at 100% Load | Max. Total Loss at 50% Load | Max. Total Loss at 100% Load | Max. Total Loss at 50% Load | Max. Total Loss at 100% Load | |||||
| 1 | 16 | 11/0.433 | 3 | 4.50% | 150 | 480 | 135 | 440 | 120 | 400 |
| 2 | 25 | 11/0.433 | 3 | 4.50% | 210 | 695 | 190 | 635 | 175 | 595 |
| 3 | 63 | 11/0.433 | 3 | 4.50% | 380 | 1250 | 340 | 1140 | 300 | 1050 |
| 4 | 100 | 11/0.433 | 3 | 4.50% | 520 | 1800 | 475 | 1650 | 435 | 1500 |
| 5 | 160 | 11/0.433 | 3 | 4.50% | 520 | 1800 | 475 | 1650 | 435 | 1500 |
| 6 | 200 | 11/0.433 | 3 | 4.50% | 890 | 2700 | 780 | 2300 | 670 | 2100 |
| 7 | 250 | 11/0.433 | 3 | 4.50% | 1050 | 3150 | 980 | 2930 | 920 | 2700 |
| 8 | 315 | 11/0.433 | 3 | 4.50% | 1100 | 3275 | 1025 | 3100 | 955 | 2750 |
| 9 | 400 | 11/0.433 | 3 | 4.50% | 1300 | 3875 | 1225 | 3450 | 1150 | 3330 |
| 10 | 500 | 11/0.433 | 3 | 4.50% | 1600 | 4750 | 1510 | 4300 | 1430 | 4100 |
| 11 | 630 | 11/0.433 | 3 | 4.50% | 2000 | 5855 | 1860 | 5300 | 1745 | 4850 |
| 12 | 1000 | 11/0.433 | 3 | 5.00% | 3000 | 9000 | 2790 | 7700 | 2620 | 7000 |
| 13 | 1250 | 11/0.433 | 3 | 5.00% | 3600 | 10750 | 3300 | 9200 | 3220 | 8400 |
| 14 | 1600 | 11/0.433 | 3 | 6.25% | 4500 | 13500 | 4200 | 11800 | 3970 | 11300 |
| 15 | 2000 | 11/0.433 | 3 | 6.25% | 5400 | 17000 | 5050 | 15000 | 4790 | 14100 |
| 16 | 2500 | 11/0.433 | 3 | 6.25% | 6500 | 20000 | 6150 | 18500 | 5900 | 17500 |
| 17 | 315 | 33/0.433 | 3 | 4.50% | 1183 | 3521 | 1102 | 3333 | 1027 | 2956 |
| 18 | 400 | 33/0.433 | 3 | 4.50% | 1398 | 4166 | 1317 | 3709 | 1236 | 3580 |
| 19 | 500 | 33/0.433 | 3 | 4.50% | 1720 | 5106 | 1623 | 4623 | 1537 | 4408 |
| 20 | 630 | 33/0.433 | 3 | 4.50% | 2150 | 6294 | 2000 | 5698 | 1876 | 7525 |
| 21 | 1000 | 33/0.433 | 3 | 5.00% | 3225 | 9675 | 2999 | 8278 | 2817 | 7525 |
| 22 | 1250 | 33/0.433 | 3 | 5.00% | 3870 | 11556 | 3548 | 9890 | 3462 | 9030 |
| 23 | 1600 | 33/0.433 | 3 | 6.25% | 4838 | 14513 | 4515 | 12685 | 4268 | 12148 |
| 24 | 2000 | 33/0.433 | 3 | 6.25% | 5805 | 18275 | 5429 | 16125 | 5149 | 15158 |
| 25 | 2500 | 33/0.433 | 3 | 6.25% | 6988 | 21500 | 6611 | 19888 | 6343 | 18813 |
A BIS distribution transformer is a low-loss transformer certified by the Bureau of Indian Standards under IS:1180 norms. It is used to step down voltage from 11/33 kV to consumer-usable levels like 440V or 230V.
BIS has defined maximum loss levels for transformers in Star 1, 2, and 3 categories. Makpower’s transformers are manufactured not to exceed these prescribed loss values, ensuring energy efficiency and cost savings.
Makpower offers both copper wound and aluminium wound transformers. Copper provides better conductivity, while aluminium is more cost-effective with lighter weight.